Post

APC1500 Test the Battery Pack

Testaufbau

An das Batteriepack kommt noch ein 50A Kfz Sicherung mit Halter. An die Gegenseite kommt der vorher gebaute Kabelsatz. img

Auf der Synology lasse ich das hier auf der Shell laufen…

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
output=200watt.csv

touch output
echo "elapsed time" | tr '\n' ',' > $output
upsc ups |  grep -E 'battery.runtime:|battery.charge:|ups.load:'         \
         | tr '\n' ','| sed 's/[^A-Za-z.,]//g' | sed 's/,\?$/\n/'        \
         >> $output 

starttime=$(date +%s)
date > timestamp.$output 
while true;                                                              \
      do                                                                 \
        echo $(($(date +%s) - starttime))| tr '\n' ',' &&                \
        upsc ups | grep -E 'battery.runtime:|battery.charge:|ups.load:'  \
                 | tr '\n' ',' | sed 's/[^0-9,]//g' | sed 's/,\?$/\n/';  \
      sleep 30;                                                          \
      done                                                               \
      >> $output

…was dann CSV…

elapsed time,battery.charge,battery.runtime,ups.load
0,100,7848,23
30,100,8100,21
60,87,7272,22
...
6583,10,896,20
6614,9,804,20
6644,9,804,20
6674,9,776,20

… aus der Rohausgabe erzeugt.

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
norman@dsm:~$ upsc ups
battery.charge: 100
battery.charge.low: 10
battery.charge.warning: 50
battery.date: 2001/09/25
battery.mfr.date: 2013/06/10
battery.runtime: 10308
battery.runtime.low: 120
battery.type: PbAc
battery.voltage: 26.0
battery.voltage.nominal: 24.0
device.mfr: American Power Conversion
device.model: Back-UPS RS 1500G
device.serial: XXXXXXXXXXXXX  
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 5
driver.parameter.port: auto
driver.version: XXXXXXXXXXXXX
driver.version.data: APC HID 0.95
driver.version.internal: 0.38
input.sensitivity: medium
input.transfer.high: 294
input.transfer.low: 176
input.voltage: 237.0
input.voltage.nominal: 230
ups.beeper.status: disabled
ups.delay.shutdown: 20
ups.firmware: 878.L4 .I
ups.firmware.aux: L4 
ups.load: 20
ups.mfr: American Power Conversion
ups.mfr.date: 2013/06/10
ups.model: Back-UPS RS 1500G
ups.productid: 0002
ups.realpower.nominal: 865
ups.serial: XXXXXXXXXXXX  
ups.status: OL
ups.test.result: No test initiated
ups.timer.reboot: 0
ups.timer.shutdown: -1
ups.vendorid: 051d

Testergebnis

MessgrößeWert
Laufzeit01:51:14
Restladung9%
Durchschnittliche Leistung175Watt
Restzeit776s

Die USV ist so konfiguriert, dass bei <10% Restladung das NAS abgeschaltet wird - daher endet hier die Messung. Mit dieser Restladung wären noch ca. weitere 15min möglich gewesen.

Aber auch so bin ich mit den 111min sehr zu Frieden und mehr als 4mal länger bei Stromausfall geschützt.

img

This post is licensed under CC BY 4.0 by the author.